Midea Aqua Tempo Super II Series Technical & Service Manual page 12

Dc inverter air-cooled chiller
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

MCAC-ATSM-201704
Power wire
Connection
wiring
Signal wire
Control type
Safety protection device
Sound pressure level
Operation water temp
Ambient temp
Note:
Specifications are based on the following conditions:
1. Cooling: chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35˚C DB.
2. Heating: heat water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6˚C WB.
3. Water side fouling factor: 0.086m
4. Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
2
mm
2
mm
dB(A)
2
˚C /kW.
10
16×4+16×1
0.75×3-core with shielding
Wired controller
1) Protection for pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-freezing protection in cooling mode.
5) Anti-freezing protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Protection for compressor over-high discharge temperature.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low ambient temperature drive-up protection
13) Low temperature protection of plate heat exchanger.
65.8
Cooling:0~20(Less than 5℃ must add antifreeze)
Heating:25~55
Cooling:-15~52
Heating:-15~24
25×4+16×1
0.75×3-core with shielding
Wired controller
72.1