Midea Aqua Tempo Super II Series Technical & Service Manual page 34

Dc inverter air-cooled chiller
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

MCAC-ATSM-201704
14.2 System check table
Press SW3 and SW4 buttons simultaneously to enter into the system check function.
No
Parameters display on DSP2
Standby: ODU address (DSP1 display) + number of on-line units (DSP1 display)
On: display frequency
0
Defrosting: dF and operating frequency flash alternately at 1s intervals frequency In case of Pb
protection, Pb and operating frequency flash alternately at 1s intervals
1
Outdoor unit address
2
Outdoor unit capacity
3
Number of outdoor units (main unit display)
4
Ambient temperature(T4) capacity revision
5
Operation modes (8: OFF; 0: Standby; 1: Cooling; 2: Heating)
6
Fan Speed 1 index
7
Fan Speed 2 index
8
Condenser tube temperature
9
Outdoor ambient temperature
10
Reserved
11
Evaporator anti-freezing temperature(Taf1)
12
Evaporator anti-freezing temperature(Taf2)
13
Total water outlet temperature(Tw)
14
Inlet water temperature(Twi, displays to decimal places)
15
Outlet water temperature(Two)
16
Total cooling outlet temperature(Tz/7)
17
Reserved
18
Compressor discharge temperature(Tp1)
19
Compressor discharge temperature(Tp2)
20
Compressor module temperature(Tf1)
21
Compressor module temperature(Tf2)
22
Air discharge superheat degree
23
Current of compressor 1
24
Current of compressor 2
25
Current of PUMP
26
EXV 1 position(step=value displayed *4)
27
EXV 2 position(step=value displayed *4)
28
High pressure
29
Low pressure (displays to decimal places)
30
Air suction superheat degree
Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)