11.2 Braking Unit and Braking Resistor Unit

For models GP5 2011, − GP5 2015 (200 V Class 11, 15 kW).
When installing a DC Reactor (option), remove the common bar between ¾1 and ¾2 terminals (provided as standard) and
=
connect a DC Reactor with the terminals.
When using the Thermal Overload Relay, set constant n070 to 0. (Stall Prevention selection during decel is disabled.) If it is not
changed, the Inverter may not stop within set decel time.
NOTE:
Braking Unit or Thermal Overload Relay cannot be connected to Inverters of 200V class 18.5 to 75kW or 400V class 18.5
to 160 kW.
Firmware – S2011 and S3012
Revision: 1 (9/98)
GP5
Figure 55 Connection Diagram for Braking Unit and Braking Resistor
Chapter 11: Typical Connection Diagram
81