6.2.2.
Custom V/f Pattern
Set each pattern when using a special motor (high-speed motor, etc.) or when requiring special torque adjustment of
machine.
Make sure to satisfy the following
conditions for setting of constants
n012 to n018.
n017 < n015 < n014 < n012
Constant No.
n012
n013
n014
n015
n016
n017
n018
∗ For 400 V class, the value is twice that of 200 V class.
Increasing the voltage of the V/f pattern increases motor torque, but an excessive increase may cause the following:
•
Inverter malfunction because of motor overexcitation.
•
Motor overheat or excessive vibration.
Increase voltage gradually while verifying the motor current.
6.3
Setting Operation Conditions
6.3.1.
Reverse Run Prohibit (n006)
"Reverse run disabled" setting does not accept a reverse RUN command from the control circuit terminal or Digital
Operator. This setting is used for applications where a reverse RUN command can cause problems.
Setting
6.3.2.
Multi-Step Selection
By combining frequency reference and input terminal function selections, up to four steps of speed can be set.
Four step speed change
n002
=
n025
=
n026
=
n027
=
n028
=
n038
=
n039
=
Firmware – S2011 and S3012
Revision: 1 (9/98)
Name
Maximum output frequency
Maximum voltage
Maximum voltage output
frequency (base frequency)
Middle output frequency
Middle output frequency
voltage
Minimum output frequency
Minimum output frequency
voltage
Description
0
Reverse run enabled
1
Reverse run disabled
1 (Operation mode selection)
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
9 (Multi-function contact input Terminal S5)
10 (Multi-function contact input Terminal S6)
Figure 18
Custom V/f Pattern Setting
Unit
Setting Range
50.0 − 400.0 Hz
0.1 Hz
0.1 − 255.0 V
0.1 V
0.2 − 400.0 Hz
0.1 Hz
0.1 −399.9 Hz
0.1 Hz
0.1 − 255.0 V
0.1 V
0.1 − 10.0 Hz
0.1 Hz
0.1 − 50.0 V
0.1 V
38
Factory Setting
60.0 Hz
[
[
200.0 V
60.0 Hz
3.0 Hz
[
[
15.0 V
1.5 Hz
[
[
10.0 V
© Saftronics, Inc.