Function

Terminating resistor

termination
Assignment of terminals
Siemens Building Technologies
HVAC Products
The SQM45... / SQM48... are of robust design and have a geartrain with only small
backlash.
Control and position feedback take place via a bus system (CAN).
The bus cable is also used for powering the actuators.
The actuators are driven by stepper motors and can be positioned with a resolution of
0.1°.
The characteristics and settings (running time, direction of rotation, limit positions) of
the SQM4... are determined by the controlling basic unit (e.g. LMV5...; for details, refer
to the Basic Documentation of the LMV...).
The running times of the associated controlling elements are varied by the basic unit
depending on the burner's control phase (e.g. startup phase: short running time; opera-
tion: long running time).
At the end of the serial bus cabling, a terminating resistor must be fitted.
For that purpose, a jumper must be set to BUS TERMINATION on the last actuator of
the bus cable, which will activate the resistor.
On all the other actuators, that jumper must be set to the other position (deactivated).
Bus
X1
X2
The 2 terminal blocks (X1 and X2) are identical.
Addressing button
LED (function code)
Jumper