Touch Screen Controller

Delete an Power peak cut schedule

1
1
-(1)
-(1)
1
1
-(2)
-(2)

Restrict operation mode (Operation mode restriction)

When using an outdoor unit that cannot operate cooling and heating at the same time, you can restrict its operation mode so
that it can only be set for either cooling or heating.
1
Tap [Operation mode restriction] in the [Functions] menu (P.53)
2
Select the operation mode and tap [OK]
NOTE
• Settings are reflected in all outdoor units.
• Even with restriction, the operation mode of the CONTROL tab can be selected. When a restricted operation mode is
selected, the Thermo OFF state is set.

Restart the Unit (System reboot)

You can restart the Unit if its operation becomes unstable.
The schedule is not executed during restart.
1
Tap [System reboot] in the [Functions] menu (P.53)
2
Tap [OK]
-EN
56
1
1
Tap [
-(2)] with [
2
Tap
3
3
3
-(1)
-(1)
Set the check box of the schedule you want to delete to
then tap [
,
The selected schedule will be deleted.
NOTE
Also, when deleting a registered time, tap
1
-(1)] (P.53)
3
-(1)]
and operate similarly.
Owner's Manual