Pilz PNOZ Seies Configuration Manual page 357

Modular safety system
Table of Contents

Advertisement

Products
Expansion modules
PNOZ ml2p
Installation
Montage_multi_allgemein
The safety system should be in-
stalled in a control cabinet with a
protection type of at least IP54. Fit
the safety system to a horizontal
DIN rail. The venting slots must face
upward and downward. Other
mounting positions could destroy
the safety system.
Use the notches on the back of the
unit to attach it to a DIN rail. Con-
nect the safety system to the DIN
rail in an upright position so that the
earthing springs on the safety sys-
tem are pressed on to the DIN rail.
The ambient temperature of the
PNOZmulti units in the control cab-
inet must not exceed the figure
stated in the technical details, oth-
erwise air conditioning will be re-
quired.
To comply with EMC requirements,
the DIN rail must have a low imped-
ance connection to the control cab-
inet housing.
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Terminal configuration
Dimensions
K l e m m e n b e l e g u n g
A b m e s s u n g e n
NSG-D-2-426-2010-03