Base units
PNOZ mm0p
Function description
The function of the safety system's in-
puts and outputs depends on the safe-
ty circuit created using the PNOZmulti
Configurator. A chip card is used to
download the safety circuit to the base
unit. The base unit has 2 microcontrol-
Wiring
The wiring is defined in the circuit dia-
gram in the Configurator. There you
can select the inputs that are to per-
form a particular safety function and
the outputs that will switch this safety
function.
Please note:
Information given in the "Technical
details" must be followed.
Outputs O0 to O3 are semiconduc-
tor outputs
Use copper wire that can withstand
75 °C.
Sufficient fuse protection must be
provided on all output contacts with
inductive loads.
Power for the safety system and in-
put circuits must always be provid-
ed from a single power supply. The
power supply must meet the regu-
lations for extra low voltages with
safe separation.
Test pulse outputs must exclusively
be used to test the inputs. They
must not be used to drive loads.
Do not route the test pulse lines to-
gether with actuator cables within
an unprotected multicore cable.
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
lers that monitor each other. They
evaluate the input circuits and switch
the outputs accordingly.
The LEDs indicate the status of the
PNOZmulti safety system.
The LC display indicates the status of
the inputs/outputs and the supply volt-
age.
The online help on the PNOZmulti
Configurator contains descriptions of
the operating modes and all the func-
tions of the PNOZmulti safety system,
plus connection examples.