Pilz PNOZ Seies Configuration Manual page 186

Modular safety system
Table of Contents

Advertisement

Products
Expansion modules
PNOZ mc6p coated version
Notice
Technical details
Electrical data
Supply voltage (U
via base unit
Power consumption at U
Times
Supply interruption before de-energisation
CANopen
Application range
Unit type
Status indicator
Station address
Transmission rate
Connection
Galvanic isolation
Test voltage
2.3
Environmental data
Vibration in accordance with EN 60068-2-6, 04/95
Frequency:
Amplitude:
Climatic suitability
EMC
Ambient temperature
Storage temperature
Mechanical data
Protection type
Mounting (e.g. cabinet)
Housing
Terminals
DIN rail
Top hat rail
Recess width
Housing material
Housing
Front
Dimensions (H x W x D)
Weight with connector
Order reference
Type
PNOZ mc6p
coated version
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
2.3-104
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the op-
)
B
B
Features
Expansion module
erating instructions supplied with the
unit.
24 VDC
Max 2.5 W
Min. 20 ms
Non-safety-related applications
Slave
LED
0 ... 99
10, 20, 50, 125, 250, 500, 800 kBit/s, 1 MBit/s
Male 9-pin connector
Yes
500 VAC
10 ... 55 Hz
0.35 mm
DIN IEC 60068-2-3, 12/86
EN 61000-6-2, 10/01
0 ... +50 °C
-25 ... +70 °C
IP54
IP20
IP20
35 x 7.5 EN 50022
27 mm
PPO UL 94 V0
ABS UL 94 V0
94 x 22.5 x 119 mm
145 g
Fieldbus module, CANopen
Order no.
773 727
NSG-D-2-377-2006-02