Technical Instructions
Document No. 155-517P25
Rev. 1, July, 2000
Switch Adjustment,
continued

Shaft Adjustment

See Figure 6.

Cam Drum Adjustment

See Figure 6.

Wiring

Electrical Connection

Grounding

Wiring connections

AGA56.1... circuit boards.
See Figures 7 and 8.
Page 8
NOTE:
SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°.
SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be
adjusted only between 0 and 90°. SQM5x.xxxxxx4 actuators have a 135°
potentiometer and the switches must be adjusted only between 0 and 135°.
The actuator shaft can be disengaged by pressing the silver shaft release button located
to the right of the auto/manual switch. The shaft can be manually rotated when the
button is pressed. Once pressed, the button can be locked by pushing it slightly
upwards. After the shaft has been manually aligned, re-engage the shaft by pushing the
shaft release button downwards.
The cam drum must be manually aligned by pressing and holding the black cam drum
release button. The cam drum must be rotated until the "0" mark on the cam drum
position scale (left scale on the cam drum) is aligned with the gray actuator position
indicating pointer.
SQM5... actuators are equipped with two removable conduit connection plates located
on the upper corner of the gear housing. Each plate is provided with two threaded
connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is
recommended.
To avoid electro-magnetic interference, the SQM5... actuators must be grounded.
The ground terminal is located to the right of the auto/manual switch.
NOTE:
SQM5... actuators require a single source, single phase power supply.
Wiring connections vary depending on which AGA56.... circuit board is installed.
1. Connect line voltage to terminal L. Terminal L must be powered to enable manual
operation.
2. Connect neutral to the double terminal block with the two gray motor wires, located
on the left side of the gray switch housing.
3. Connect line voltage to terminal A to drive the actuator in the opening direction.
4. Connect line voltage to terminal Z to drive the actuator in the closing direction.
Siemens Building Technologies, Inc.