Wiring The System - HID ACW2-XN Installation Manual

Web-based access control solution
Hide thumbs Also See for ACW2-XN:
Table of Contents

Advertisement

Web-Based Access Control Solution
ACW2-XN
7
AW2 Wiegand Module
AW2 Module Cable Specifications
Application
Door Strike (12V and higher)
Card Reader
Door Contact
Request-to-Exit
MOV (included in the packaging) Specification
MOV Rating
Where to use the suppled MOVs
The MOVs MUST be connected across 12V inductive loads to prevent sparking at the
relay contacts.
The supplied MOVs are only for 12V applications, and are MANDATORY
Supervised Inputs (Optional)
HID Access Manager can monitor the Door Position Sensor (DPS) circuits for tampering
when resisters are installed.
Two 1kΩ resistors are required for every sense line. These should be installed in a
location where they cannot be accessed without opening the door in question:
This feature must be activated in HID Access Manager via the door configuration
process.
Page 8 of 26

Wiring the System

Conductors
(# of Wires)
2
10 (8 used)
2
4
25V
500A 77V
RMS
Max Clamping
COM
NC
Installation Guide
Cross Sectional Area
2
0.75 mm
, 0,0012 in
2
0.32 mm
, 0.0005 in
2
0.32 mm
, 0.0005 in
2
0.32 mm
, 0.0005 in
0V
+12V
© 2018 HID Global Corporation All rights reserved.
AWG
Max Cable Length
2
18
150 m, 492 ft.
2
20
150 m, 492 ft.
2
20
150 m, 492 ft.
2
20
150 m, 492 ft.