One Acw2-Xn Enclosure; Example Using Three Aw2 Wiegand Modules - HID ACW2-XN Installation Manual

Web-based access control solution
Hide thumbs Also See for ACW2-XN:
Table of Contents

Advertisement

Web-Based Access Control Solution
ACW2-XN
5
One or two ACW2-XN enclosures?

ONE ACW2-XN enclosure

is sufficient for up to 8 readers
AND if all doors are within reasonable cabling distance of the enclosure
TWO ACW2-XN enclosures are needed
for 9 to 16 readers
OR if a second group of doors is a significant distance away from the first group. The two
enclosures are linked with an RS-485 cable, saving on long, multiple-reader cable runs.
(Remember that the total door count still cannot exceed the 16-door limit.)
How many AW2 Modules are needed?
One AW2 Module is needed for each door that has both entry and exit readers.
One AW2 Module is needed for every TWO doors that only require entry readers
NOTE:
Any combination of single-readers and two-reader doors is permissible
Readers may be independently allocated to any door
Whatever the combination, no more than sixteen doors are supported

Example using three AW2 Wiegand Modules:

Page 4 of 26
System Architecture – Best Practices
Any combination of single-reader or entry+exit-reader doors is possible
Installation Guide
© 2018 HID Global Corporation All rights reserved.