Siemens SIMATIC FM 452 Manual page 84

Electronic cam controller installation and parameter assignment
Table of Contents

Advertisement

Machine Data and Cam Data
Address
Name
24.0
DISP_REV
With the machine data "distance per encoder revolution" you inform the FM 452 of the distance
covered by the drive system per encoder revolution.
The value "distance per encoder revolution" depends on how the axis is set up and how the encoder is
installed. You must take into account all transmission components such as couplings or gearing.
Section 8.6 (Page 8-20) describes the relationship between the machine data "distance per Encoder
Revolution" and "increments per encoder revolution".
Motor
Encoder
Motor
8-16
Type
Initial Value
DINT
L#80000
Gearing
Gearing
Comment
Distance per encoder revolution :
Range of values:
1 m to 1 000 000 000 m
Encoder
FM 452 Electronic Cam Controller
C79000-G7076-C452-04