Changeover Of Acting Direction - Siemens Acvatix SAX Series Basic Documentation

Hide thumbs Also See for Acvatix SAX Series:
Table of Contents

Advertisement

DIL switches
Selecting the acting
direction
SAX61.03
SAV61.00
SAY61P03
SAX61P03
SAV61P00
Siemens
Building Technologies
4.3.2

Changeover of acting direction

Direct acting
1)
OFF
positioning signal Y or Z
1)
Factory setting: All switches set to OFF
· With valves whose stem is extended in the fully closed position, "direct acting"
means that the valve is fully closed (0%) when positioning signal Y = 0 V resp.
Z = 0 Ω. This applies to all Siemens valves according to "Equipment
combinations" (page 14).
· With valves whose stem is retracted in the fully closed position, "direct acting"
means that the valve is fully open (100%) when positioning signal Y = 0 V resp.
Z = 0 Ω.
Y, Z
Positioning signal
V
Volumetric flow
Acting direction: Direct
Acting direction: Reverse
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
Acting direction
Reverse acting
1)
ON
positioning signal Y or Z
Direct acting
Positioning signal Y:
DC 0...10 V
4...20 mA
0...1000 W
Positioning signal Z:
Reverse acting
Positioning signal Y:
DC 0...10 V
4...20 mA
0...1000 W
Positioning signal Z:
Reverse acting
Direct acting
59 / 92
CE1P4040en
2018-12-05