Function Module Azx61.1; Sequence Control (Signal Adaptation) - Siemens Acvatix SAX Series Basic Documentation

Hide thumbs Also See for Acvatix SAX Series:
Table of Contents

Advertisement

DIL switches
DIL switches
HEX switches
Notes
Siemens
Building Technologies
4.3

Function module AZX61.1

Acting direction
1)
OFF
Direct acting positioning signal Y or Z
1)
ON
Reverse acting positioning signal Y or Z
1)
Factory setting: All switches set to OFF
The funktion module may not be used in combination with SAX61.03/MO.
4.3.1

Sequence control (signal adaptation)

Sequence control
1)
ON
Sequence control (signal adaptation)
1)
Factory setting: All switches set to OFF
Nr.: 1
· Can only be used with voltage input.
· Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator
operates on DC 0...10 V.
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
Setting sequence control
Rotary switches LO and UP are used to set the starting point or
working range of a sequence.
Position
Starting point
"LO"
0
0,3 V
1
1 V
2
2 V
3
3 V
4
4 V
5
5 V
6
6 V
7
7 V
8
8 V
9
9 V
A
10 V
B
11 V
C
12 V
D
13 V
E
14 V
F
15 V
Invalid HEX switches combinations
LO
0
1 2 3
4
5
6
UP
F F F F F
F
UP
E
UP
UP
UP
Sequence control
Sequence control not active
Sequence control
(signal adaptation)
Position
Working range
"UP"
0
9,4 V
1
3 V
2
4 V
3
5 V
4
6 V
5
7 V
6
8 V
7
9 V
8
10 V
9
12 V
A
14 V
B
16 V
C
18 V
D
20 V
E
25 V
F
30 V
7
8
9
A
B
C
D
E F
F
F
F
F
D D
C
C B
E
E
E
E
E
E
D
D C
F
F
E
E D
F
F E
57 / 92