Spare Parts; Sizing; Parallel Operation Of Actuators - Siemens Acvatix SAX Series Basic Documentation

Hide thumbs Also See for Acvatix SAX Series:
Table of Contents

Advertisement

SAY.., SAX.., SAV..
SAL..
SA..31.. and SA..81..
SA..61..
SAX61../MO
22 / 92
Siemens
Building Technologies
2.8

Spare parts

The following spare part sets are available:
Stock number
8000060843
Single components from the spare part sets are not available.
Stock number
8000060844
Single components from the spare part sets are not available.
2.9

Sizing

2.9.1

Parallel operation of actuators

3-position actuators must have one specific controller each, refer to "Connection
diagrams" (page 82).
Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA.
Modulating actuators have an input impedance of 100 kΩ.
The Modbus converter is designed for analog control on 0..10 V on the actuator
side.
Note: Keep the setting of the analog signal on the actuator as is (switch 1 to
"OFF"), adjustment is not allowed.
The actuators are factory-set to equal-percentage characteristic curve.
Note: The DIL switch (actuator-internal changeover of characteristic curve) must be
set to "log" (switch 2 to "OFF").
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Engineering
Housing cover
Screw
(valve stem coupling)
U-bracket
Housing cover
2 adapters
1 pc. 14 mm
1 pc. 11 mm
4 screws
2 pcs. M5 x 20 mm
2 pcs. M6 x 20 mm
CE1P4040en