Siemens Acvatix SAX Series Basic Documentation page 79

Hide thumbs Also See for Acvatix SAX Series:
Table of Contents

Advertisement

Environ-
Operation
mental
Climatic conditions
conditions
Mounting location
Temperature General
Humidity (noncondensing)
Transport
Climatic conditions
Temperature
Humidity
Storage
Climatic conditions
Temperature
Humidity
Max. media temperatur when mounted
on valve
Directives
Product standard
and
Electromagnetic compatibility
Standards
EU Conformity (CE)
RCM Conformity
EAC Conformity
UL, cUL
Environ-
mental
compati-
bility
Dimensions
Weight
Excl. packaging
Accessories
Potentiometer ASZ7.5
8)
Auxiliary switch ASC10.51
External supply line protection
US installation, UL & cUL
Stem heating element ASZ6.6
Function module AZX61.1 for SA..61..
External supply line protection
US installation, UL & cUL
Siemens
Building Technologies
IEC 60721-3-3
Class 3K5
Indoors (weather-protected)
-15...55 °C
5...95% r.h.
IEC 60721-3-2
Class 2K3
-25...70 °C
<95% r.h.
IEC 60721-3-1
Class 1K3
-15...55 °C
5...95% r.h.
130 °C
EN60730-x
For residential, commercial and industrial environments
(Application)
A5W00000333
AC 230 V A5W00000334
AC 230 V -
AC/DC 24 V UL 873 http://ul.com/database
The product environmental declarations contain data on environmentally
compatible product designs and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal):
7173310559Ben
See "Dimensions" (page 84)
See "Dimensions" (page 84)
0...1000 Ω ± 5%
Voltage
DC 10 V (SELV)
Current rating
< 4 mA
AC 24...230 V, 6 (2) A, floating
Switching capacity
See section power supply
AC 24 V class 2, 5 A general purpose
AC / DC 24 V ± 20%
Power supply
Power consumption
50 VA / 30 W
at 50 Hz
Inrush current (cold)
Max. 8.5 A (max. Temperatur 85 °C / 185 F)
Switching capacity
AC 24...230 V, 6 (2) A, floating
See section power supply
AC 24 V class 2, 5 A general purpose
1)
Observe acting direction of DIL switches
2)
AWG = American wire gauge
3)
Also with weather shield ASK39.1
4)
SAL.T20 / T40 have a minimum holding torque of 14 Nm
5)
Up to 150 °C with horizontal mounting position
6)
SAX61../MO is not suitable for outdoor applications.
7)
The documents can be downloaded from http://siemens.com/bt/download.
8)
UL recognized component
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Technical data
SAY..
SAX..
6)
130 °C
SAY..
SAX..
1)
7)
CE1T4501x1
1)
7)
CE1T4515X4
Eurasia conformity for all SA..-variants
7173310559Ben
7)
A6V101083254
SAV..
5)
130 °C
120 °C
SAV..
7)
CE1T4503xx
CE1T4502X1
7)
CM1T4503_C1
7)
7)
7173310522A
CE1E4502en
7)
SAL..
SAL..
7)
-
7)
79 / 92
CE1P4040en
2018-12-05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents