Function
Positioning times with specified nominal
data
stroke / nominal angular rotation
Positioning force
Torque
Nominal stroke
Angular rotation
Signal
Positioning signal "Y"
inputs
SA..31..
SA..81..
SA..61.. (DC 0...10 V)
SA..61.. (DC 4...20 mA)
Communi-
Communications protocol
cation
Parallel
SA..61..
operation
Forced
Positioning signal "Z"
control
Position
Position feedback U
feedback
Connecting
Wire cross-sectional areas
cable
Cable entries
Degree of
Housing from vertical to horizontal
protection
Insulation class
Actuators SA..31..
Actuators SA..61..
Actuators SA..81..
78 / 92
Siemens
Building Technologies
SAX..00, SAV.., SAL..00
SAY..03, SAX..03..,
30 s
SAL..03
200 N
SAL..T10
4)
SAL..T20
4)
SAL..T40
15 mm
SA..31.., SA..81.. 3- position
Voltage
AC 230 V ± 15%
Voltage
AC 24 V ± 20% / DC 24 V + 20% / -15%
Current draw
≤ 0,1 mA
Input impedance
≥ 100 kΩ
Current draw
DC 4...20 mA ± 1%
Input impedance
≤ 500 Ω
Modbus RTU
RS-485, not galvanically separated
Max. 32
Number of nodes
1...247 / 255
Address range
Factory settings: 255
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Transmission formats
Factory settings: 1-8-E-1
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Baud rates (kBaud)
Factory settings: Auto
120 Ω electronically switchable
Bus termination
Factory settings: Off
≤ 10 (depending on controller output)
SA..61..
R= 0...1000 Ω, G, G0
R = 0...1000 Ω
Stroke / rotation proportional to R
Z connected to G
Max. stroke 100%
Z connected to G0
Min. stroke 0%
Voltage
Max. AC 24 V ± 20%
Max. DC 24 V + 20% / -15%
Current draw
≤ 0,1 mA
SA..61..
DC 0...10 V
Load impedance
>10 kΩ res.
Load
Max. 1 mA
0.13...1.5 mm
SA..
EU:
SA..U
US:
SAX61../MO
Fixed connecting cable: 0.9 m
Number of wires: 5 x 0.75 mm
IP54 as per EN 60529 3)
As per EN 60730
AC 230 V
II
AC / DC 24 V
III
AC / DC 24 V
III
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Technical data
SAY..
SAX..
120 s
30 s
800 N
-
-
-
20 mm
-
1)
1)
2
2)
, AWG 24...16
2 entries Æ 20.5 mm (for M20)
1 entry Æ 25.5 mm (for M25)
3 entries Æ 21.5 mm for ½" tube
connection
2
SAV..
SAL..
120 s
120 s
-
30 s
1600 N
-
-
10 Nm running
-
20 Nm running
-
40 Nm running
40 mm
-
-
90°
1)
90°
1)