Advertisement

Mechanically
Notes
Electrically
SA..61..
General notes on
calibration
46 / 92
Siemens
Building Technologies
3.2

Commissioning and operation

3.2.1

Function check and Calibration

Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 77)
· Actuator is mechanically connected to a Siemens valve
· Actuator is in "Manual operation" mode (page 73).
The actuator can be operated with the help of the "Manual adjuster" (see page 73).
Stroke
Manual adjuster
actuator
Actuator's
Turning in clockwise
stem
direction
extends
Turning in counter-
Actuator's
clockwise direction
stem retracts
· Ensure that the actuator's and valve's stem, or actuator's and valve's spindle are
securely connected in all positions.
· If the actuator is forced to travel beyond its end positions, overload protection
responds.
· Observe information given in chapter "Acting direction and flow characteristic"
on page 61.
Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 77).
· Actuator is mechanically connected to a Siemens valve.
· Actuator is in "Automatic" mode (page 73).
Actuator and, if required, accessories are correctly fitted and connected. Also refer
to "Connection Terminals" (page 81)
· Power is applied.
Calibration is required with modulating actuators and SA..61.. before the function
check.
Before making the calibration, the following preconditions must be satisfied:
· A description of the calibration function is given in chapter "Calibration" (page 64
for non-Modbus actuators, page 68 for Modbus actuators).
· Housing cover is removed (step 6 "Special notes on mounting", page 36).
1
Bridge contact
If required, calibration can be repeated any number of times.
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Handling
Rotary actuator
Actuator's spindle turns in
clockwise direction
Actuator's spindle turns in
counterclockwise direction
2
Check LED (page 74)
Control path
Bypass valve
valve AàAB
B à AB
Opening
Closing
Closing
Opening
CE1P4040en