Indicators - Siemens Acvatix SAX Series Basic Documentation

Hide thumbs Also See for Acvatix SAX Series:
Table of Contents

Advertisement

Operational status
indication
Position indication
Status indication (LED)
74 / 92
Siemens
Building Technologies

4.14.4 Indicators

In Automatic mode, the manual adjuster serves for the indication of travel. See
"Automatic" (page 73).
Position indication is on 2 opposite sides. When turning the manual adjuster, the
indicator moves in the same direction.
The scale indicates the stroke. When reaching the stops, the valve is either fully
open or fully closed.
Housing cover fitted
When the housing cover is fitted, the LED can be
viewed through a light conductor.
The status indication informs about the operational state of the actuator.
LED
Indication
Operating state
On
Automatic mode
Blinking
Calibration (page 46).
Green
In manual mode
Detection of foreign bodies
(page 65 / page 67)
On
Calibration error
Red
Blinking
Clogged valve
Dark
Dark
No power or electronics faulty
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
A
Indication of travel
B
Scale
Position indication
C
Indicator
D
LED Status indication
Housing cover removed
When the housing cover is removed, the LED
can be viewed through a hole.
Remarks, troubleshooting
Normal operation
Wait until calibration is finished
(then green or red light)
Manual adjuster in MAN position
Check valve / actuator
Start calibration again (page 46)
Check valve
Check operating voltage
CE1P4040en
2018-12-05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents