Failure, Switchover and Return of Fault-tolerant Components

6.7 OS clients

PC station identified as faulty
Additional information on this is available in the section "Failure, failover and restarting of
redundant OS servers (Page 181)".
Additional information
● Manual
6.7
OS clients
6.7.1
Failover reactions of OS clients with permanent operability
Functionality
If the network for the configured OS server is interrupted, the process values on the OS clients
are no longer updated and process control is no longer possible. Other OS clients connected
to the redundant OS partner server are not affected by this. The plant operator can therefore
switch to these OS clients, if needed.
Example configuration
188
Process Control System PCS 7; SIMATIC Route Control
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02