Diagnostics

Information is available in the manual
Diagnostics .
PCS 7 features advanced self-diagnostics for redundant software systems (servers). If this
diagnostics routine detects an internal fault, and in the event that the redundant partner server
is fully functioning, all communication connections on the server affected by the fault are
disconnected (terminal and system bus).
The affected server is then restarted automatically.
Requirements
● Use of a PCS 7 OS (multi-station) redundant system, SIMATIC BATCH and SIMATIC Route
● The following settings have been made on the server systems:
Procedure
1. Go to the Windows Start menu and open the "Run" dialog box.
2. Enter the following in the input field:
3. In the tree view, select the folder Local Computer Policy > Computer Configuration >
4. Double-click the "Display Shutdown Event Tracker" object in the detail view.
5. Select the "Deactivated" option button.
6. Click "OK".
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02
Control.
– Automatic Windows logon (not relevant for servers in WinCC service mode)
– Automatic start of the PCS 7 server applications
gpedit.msc
The "Local Group Policy Editor" dialog window opens.
Administrative Templates > System.
The "Display Shutdown Event Tracker" dialog box opens.
Note
Before a PCS 7 server application is exited, an availability check is carried out on the
relevant redundant partner server. If the partner server is not fully functional, the user is
informed of this status and can proceed accordingly.
The availability check is only carried out in service mode if a user is logged on.
Process Control System PCS 7; Service Support and
7
209