How To Configure A Redundant Connection Between A Route Control Server And As - Siemens SIMATIC PCS 7 Function Manual

Fault-tolerant process control systems (v8.0)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Advantages of fault-tolerant components
4.7 SIMATIC Route Control stations
Additional information
● Manual
4.7.4

How to configure a redundant connection between a Route Control server and AS

Introduction
The redundant connections between the Route Control server and the AS are created in
NetPro using SIMATIC Route Control wizards.
Requirements
● The PCS 7 project is open in SIMATIC Manager.
● The AS is connected to the plant bus in NetPro.
● The plant bus has been configured.
● Two SIMATIC PC stations have been configured in HW Config as a Route Control server
Procedure
1. In the SIMATIC Manager, select the menu command Options > SIMATIC Route Control >
2. In the "Introduction" dialog box of the wizard, click "Next".
3. In the "Generate S7 connections" group, activate the check box "AS-Server connection
162
Process Control System PCS 7; SIMATIC Route Control
and Route Control partner server with the following network adapters.
Wizard.
The "What do you want to do?" dialog box opens.
information". Click "Next".
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02