Siemens SIMATIC PCS 7 Function Manual page 129

Fault-tolerant process control systems (v8.0)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

13.Select the menu command Insert > Station > SIMATIC PC Station.
14.Select the SIMATIC PC station, select the menu command Edit > Object Properties and
15.Enter the Windows name of the computer to be used as the OS partner server in the
16.In the component view, select the SIMATIC PC station and double-click the "Configuration"
17.If the hardware catalog is not visible, select the menu command View > Catalog.
18.In the hardware catalog under "SIMATIC PC Station > HMI...", select the "WinCC
19.Select the communication processor (CP 1623 or CP 1613) from the SIMATIC PC Station
20.Set the required address on the bus for the CP.
21.Repeat steps 19 and 20 for the second communication processor (CP 1623 or CP 1613).
22.Select the menu command File > Save and exit HW Config.
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02
A new SIMATIC PC station is inserted in the selected project.
enter the desired name (in the example, OS partner server).
"Computer name" box.
object in the detail window.
The hardware configuration of the SIMATIC PC station opens.
The hardware catalog opens.
application (stby)" and insert it in the configuration table by means of drag-and-drop.
> CP Industrial Ethernet folder of the hardware catalog and drag it to the PC station.
The "Properties - Ethernet Interface" dialog box opens.
Select the "Set MAC address/Use ISO protocol" check box and click "OK".
Advantages of fault-tolerant components
4.5 Operator stations
129