Lightning Protection International Stormaster ESE 15 Installation Manual page 43

Table of Contents

Advertisement

The Stormaster ESE terminal must NOT be used as a slinging point
When lifting the mast, ensure that the slings or ropes cannot damage the Stormaster ESE
terminal. See Figure 38
Sling in at
least two places
Stress removed from upper
termination by securing
downconductor to lower mast
with flat webbing or other
appropriate sling
Figure 38.
When lifting the mast, the HVSC Plus downconductor must be tied off to the mast to
remove any strain on the HVSC Plus downconductor termination to the Stormaster ESE
terminal
Protect the HVSC Plus downconductor at the base of the mast when lifting, maintain
a minimum bending radius of 430 mm and ensure it does not drag over rough or sharp
surfaces
www.lpi.com.au
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
Do not sling at base
Do not lift with more
than 5 m (17 ft) of
downconductor
Max 5 m
hanging from mast
(17 ft)
without tying off
to mast
41