HVSC Plus cable has an outer diameter of approximately 35 mm and has an aluminium
stranded centre conductor and copper tape screen (which can be easily seen from the
end of the cable).
This termination kit will not work with any other cable.
Tools and parts required for the completion of HVSC Plus lower termination include:
Compression or mechanical crimping tool (for 70 mm² crimp lug)
Sharp knife
Shifting spanner (or 17 mm A.F. spanner/socket)
Rubber gloves
Tape measure (metric)
Lower Termination Kit consists of:
Instructions
1 x Roll of waterproofing mastic tape
1 x 70 mm² crimp lug
2 x Warning labels
U-Bolt earth clamp
1 x Tube of conductive paste
The following steps outline the termination of the lower end of the HVSC Plus to the
lightning earth.
The diagram below shows the different layers of the HVSC Plus cable and indicates
their names as referred to in the following instructions:
Black Inner
Filler
Inner Aluminium
Conductors
Figure 16.
www.lpi.com.au
Black Insulation
with Semiconductive Outer
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
Black
Outer Sheath
Outer Copper
Screen Tape
27