Installation of the Lightning Earth

Before installation of the lightning protection earth, consult site drawings of underground
services so that these are not damaged during installation of the earthing system.
Earth DC resistance (typically ‹10 ohms) and impedance (typically ‹30 ohms) is required for
successful operation of LPI Stormaster ESE.
LPI recommends the installation of a radial lightning earth as shown in figure 10.
It is recommended to install a 3 x 10 metre length radial trench
Each radial should consist of a trench (Approx: 500 mm Deep x 200 mm wide x 10 m length)
An earth rod should be driven at the end of each trench
All rods should be interconnected through the use of 25 x 3 mm copper tape. The use
of earth rod clamps to fix the tape to rods is recommended
Earth Rod Clamp
Ordering Code: RTC253
Earth Rods
Ordering Code: CBER1214
Figure 10.
www.lpi.com.au
25 x 3 mm typically
3 radial lengths of 10 m,
with 500 mm depth.
Ordering Code: FL6T253C
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
Earth Pit (Polymer)
Ordering Code: EPIT-P
Lower Termination
Ordering Code: LTERMKIT - MK3
Each radial trench is treated
with earth enhancing compounds
Ordering Code: GRIP-10
RESLO-10
SRIM-20
17