MAST BUTT ADAPTOR
Figure 14.
As direct and straight as possible
Avoid sharp bends. Bend radius must not be smaller than 20 cm
Avoid routing along or across electrical conduits
Use three fasteners per metre
Protect against the risk of mechanical impact damage with guard tubes up to a height
of at least 2 m above the ground level
Natural components:
External interconnected steel frames (metal structures) may be used in place of
dedicated downconductors if it is shown that the electrical continuity / resistance is
≤ 0.1 W
24
LIGHTNING PROTECTION INTERNATIONAL PTY LTD
MAST BUTT ADAPTOR
www.lpi.com.au