Connection of Factory Pre-Terminated HVSC (Upper
End) to Guardian CAT Terminal
Tools required for the installation of the factory completed upper termination include:
• Sharp Knife.
• Medium size Phillips head screw driver.
1. Firstly remove the protective packaging from the cable and upper terminated end section
taking care not to cut cable or associated upper termination parts in the process.
2. Using a Phillips Head screwdriver, remove the M6 Phillips Head screw holding the mast butt
adaptor (if fitted) to the lower connector and retain both screw and mast butt adaptor.
3. Feed the HVSC cable through the FRP support mast.
4. Slide the black plastic mast butt adaptor back onto the brass lower connector, line up holes
and screw the Phillips Head screw into position tightly. Now screw the mast butt adaptor into
the Guardian CAT terminal and tighten the M6 Grub Screw at the base of the terminal to lock
the assembly.

Labelling

Warning Labels are supplied with all Guardian CAT terminals and should be installed as per the
following:
• In locations where personnel may be in close proximity to the HVSC Downconductor.
• Where the HVSC downconductor connects to the earthing system.
• At the base of the support mast.
There are 2 Warning Labels supplied in the front cover of this manual and also 2 supplied
in the lower termination kit. If more labels are required, contact your nearest LPI supplier or
Distributor.