Lower Termination Of Conventional Downconductor To The Lightning Earth - Lightning Protection International Guardian System 5 Installation Manual

Table of Contents

Advertisement

STEP 1.
HVSC
Downconductor
Earth Rod Clamp
Earth Rod
Figure 21.
Lower Termination of Conventional
Downconductor to the Lightning Earth
• If installing stranded copper cable as a downconductor then the lower end should be
connected to the lightning earth through the use of an earth rod clamp and then wrapped
with waterproofing tape to avoid oxidisation.
• If installing copper tape (25mm x 3mm) as a downconductor then the lower end should be
directly connected to the lightning earth through the use of a suitable earth rod clamp and
then wrapped with waterproofing tape to avoid oxidisation.
Document 36 II Guardian
Version 1.02
Guardian Install Manual V12.indd 29
STEP 2.
© Copyright 2008 LPI
Ground Level
HVSC
Downconductor
Waterproofing
Tape
Earth Rod
27
22/9/08 4:25:25 PM