• If it is necessary to isolate the HVSC downconductor from the structure, run the cable in
an insulating conduit with a minimum wall thickness of 3mm (1/8in.). The maximum
length isolated from the structure should be 2.5m (9ft). The entire length of the HVSC
downconductor cannot be run in insulated conduit.
• HVSC Downconductor should be protected from damage at the lower end by installing a
"Top Hat" surface mount cover of no more than 2m from ground level.
The HVSC downconductor must be checked by an LPI representative if it is damaged during
installation to see if the damage will affect performance.
INCORRECT
CORRECT
Figure 12.
Document 36 II Guardian
Version 1.02
Guardian Install Manual V12.indd 21
Radius < 500mm
Radius > 500mm
2m Max.