Horizontal Flue Terminal Installation - Lochinvar ECOKNIGHT EKW86CE Installation, Commissioning, Maintenance And User Instructions

Floor standing gas fired condensing circulating type water heater
Table of Contents

Advertisement

10.12

HORIZONTAL FLUE TERMINAL INSTALLATION

10.12.1
TYPE C
(H
ORIZONTAL ROOM SEALED
13
10.12.2
HORIZONTAL ROOM SEALED APPLICATION, MODELS EKW46CE-EKW116CE
10.12.3
HORIZONTAL CONCENTRIC ROOM SEALED APPLICATION, MODELS EKW146CE-EKW236CE
When the Water Heater is installed as a Type C
installed as follows:
1.
Determine the location of the flue terminal, taking into account minimum distances as detailed in Section
10.6.1 And the relevant British Standards.
2.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The diameter
of the hole should be no more than 10mm greater than the diameter of the air supply pipe of the terminal.
3.
Determine the required length of the terminal and cut as necessary.
When determining the required length for the flue terminal, the outer wall plate or rosette should
be flush to the wall. (see 10.12.4 )
Once cut; remove all burrs and sharp edges
4.
Insert the terminal into the drilled hole. The terminal section should be installed level or with a fall to outside
(Max. 10mm per metre) to prevent the ingress of water.
When inserting the terminal, ensure the air intake section is at the bottom.
5.
Fill the void between the terminal and wall with water resistant sealant.
6.
Fit the wall plates or rosette using appropriate fixings.
)
(Horizontal concentric) appliance, the flue system should be
13
32