Ring Redundancy
Display in "Operation" field:
forwarding: this port is switched on and has a link.
blocked: this port is blocked and has a link
disabled: this port is disabled
not-connected: this port has no link
Figure 6: Ring Redundancy dialog
In the "Ring Recovery" frame, select 200 ms.
Note: If selecting 200 ms for the ring recovery does not provide the ring
stability necessary to meet the requirements of your network, you select
500 ms.
Note: Settings in the "Ring Recovery" frame are only effective for
devices that you have configured as ring managers.
Under "Configuration Redundancy Manager", activate the advanced
mode.
Activate the ring manager for this device. Do not activate the ring
manager for any other device in the MRP-Ring.
Leave the VLAN ID as 0 in the VLAN field.
Switch the operation of the MRP-Ring on.
Click "Set" to temporarily save the entry in the configuration.
UM Redundancy Configuration L2E
Release 7.1 12/2011
2.2 Example of a MRP-Ring