Position VMAX 450F, VMAX 850F, VMAX 950F Bays

Dimensions for array layouts

Site Planning Guide VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS
54
Placing arrays in the data center or computer room involves understanding
dimensions, planning for cutouts, and ensuring clearance for power and host cables.
On nonraised floors, cables are routed overhead. An overhead routing bracket is
l
provided to allow easier access of overhead cables into the bay
On raised floors, cables are routed across the subfloor beneath the tiles.
l
Ensure there is a service area of 42 in (106 cm) for the front and 30 in (76 cm) for
l
the rear of each system bay.
The following figure shows the layout dimensions:
Figure 7 Layout Dimensions, VMAX 450F, VMAX 850F, VMAX 950F
.25 in. (.64 cm) gap
between bays
24 in.
24.02 in.
(61.01 cm)
(61 cm)
47 in.
(119 cm)
Includes
front and
rear doors
Rear
Front