Requirements For Third Party Racks With Vertical Pdus (Rear-Facing - Dell EMC VMAX 250F Site Planning Manual

All flash. with hypermax os
Table of Contents

Advertisement

Dim Label
Description
l
l
l
j
≥ 6" (15.24cm) is a requirement.
Distance between rear-facing surface of vertical PDU and the rack post or any other parallel surface
that may interfere with the power cables.
Note
k
= min depth: b+c
Where:
l
l
l
pw
= PDU width
f
= recommended minimum of 3" (7.62cm)
g
= rear rack post width (if any)
pw
f
g
+ ½" (1.3cm) ≤
+
k
: Dimension
is dependent on this value.
j
≥ 6" (15.24cm) is a requirement.
j
IF
is ≥ 6" (15.24cm), min rack depth = 43" (109.2cm).
j
IF
is < 6" (15.24cm), min rack depth = 43" (109.2cm) + distance required to make
(15.24cm).

Requirements for third party racks with vertical PDUs (rear-facing)

Third Party Racking Option for VMAX 450F, VMAX 850F and VMAX 950F
j
≥ 6"
101