Bay layout and dimensions

On nonraised floors, cables are routed overhead. An
l
overhead routing bracket is available for purchase to allow
easier access of overhead cables into the bay.
On raised floors, cables are routed across the subfloor
l
beneath the tiles.
For the system bay, ensure the following:
l
A service area of 42 in (106 cm) for the front.
n
A service area of 30 in (76 cm) for the rear.
n
Width 24.0 in.
Height 75.0 in.
Depth 39.37 in.
(not including bezels)
Site Planning Guide VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS
44
Placing arrays in the data center or computer room involves understanding
dimensions, planning for cutouts, and ensuring clearance for power and host cables.
Figure 2 Cabinet dimensions and clearances
(60 cm)
(190 cm)
(98.425 cm)
30 in. (76 cm)
24 in.
service area
24.02 in.
(61 cm)
(61.01 cm)
Rear
41.25 in.
(104.8 cm)
Includes
front
bezels
Bezel
Front
42 in. (106 cm)
service area
Rear Access
30.00 in.
(76 cm)
Front Access
42 in.
(106 cm)
.25 in. (.64 cm) gap
between bays
39.37 in.
(100.0 cm)