INTELLIGUARD 9000
The Inputs table defines each of the individual input points. PRO9000 Software
accepts a maximum of 512 input points. Each input point has 10 fields to define it.
Move from field to field by pressing Tab. Program a specific input point for the I9000
as follows:
1. Press F9 to open the Input Points table. See Fig. 14.
Fig. 14. Input Points table.
The Input Points table has the following fields:
Reference
Select either the control unit (CU) or any device on the two
communication ports.
Input
Select the input points of a device.
Message #1
The first 14-character message after the input number. This
message must already exist in the Messages table for PRO9000 to
accept the message.
Message #2
The second 14-character message after the input number. This
message must already exist in the Messages table for PRO9000 to
accept the message.
Number assigned after the second message. For example, if there
Log
are five overhead doors in a specific area Overhead Door #5
appears.
Area
Area assigned to the specific point.
Type
Number that defines how the I9000 reacts when this input is
activated. Field values are 1 through 22. See the worksheet in
Appendix A for a definition of these values.
KID
Number (1 to 4 starting from the top LED) of the area keypad LED
assigned to this detection point. The numbers refer to the bottom
four LED on the KID, (numbered from top to bottom).
Func.(tions)
The function number this input activates. (Type 10 for 24 hours,
type 19 only when armed, or type 12 access is valid.)
25

Programmable Fields

74-3046