The Relay Functions table defines what activates an output and for how long that
output remains activate.
1. Press F8 to display the Relay Functions table. See Fig. 12.
Figure 12. Relay Functions table.
No
The number of the relay function taken from the table in Fig. 11.
Type
The type of function that determines what causes that function to
activate. For example, Burglary = type 2.
Area Mask
The area or areas that affect this function. If assigned to multiple
areas, do not put a comma between the area numbers. For
example if assigned to areas one and two, type 12.
Latch.
The minimum activation time (in seconds) for each function. If a
door opens and closes immediately, the latching delay keeps the
function activated. A value of 0 means there is no latching delay.
Cut-Off
The maximum activation time of the function. If a door stays open,
the function resets at the cut-off time. A value of 0 means there is
no cut-off time.
NOTE: A function used to activate a dialer should have a 30 second latch and
no cut-off. A function used to activate a siren should have a 300
second latch and a 300 second cut-off (bell).
2. Enter the relay type in the Type field.
3. Press Tab to move to the Area Mask field.
4. Type the areas affected by the relay. Do not separate multiple areas with a
comma.
5. Press Tab to move to the Latch. field.
23

Programmable Fields