Table 5
Control Constants (`nr
Control
Constant No.
Name
Unit
Setting Range
Setting Value
Prior to
Factory Shipment
rl -01
Max Frequency (F
MAX)
0 1 Hz
500 - 400 0 Hz
60 Hz
02
Max Voltage (V
MAX)
0 1 V
0 0 - 4600V
400 V
03
Max Voltage Freq (F
A)
0 1 Hz
0 0 - 400 0 Hz
60 Hz
04
V/f Constant (F B)
0 1 Hz
0 0 - 400 0 Hz
3 Hz
05
V/f Constant (V C)
0 1 V
0 0 - 4600V
26V
06
Min Output Freq (F
MIN)
0 1 Hz
0 0 - 400 0 Hz
1 5 Hz
07
Min Output Freq Voltage (V
MIN)
0 1 V
0 0 - 460 0 V
14 V
08
Accel Time
0 1 s
0 1 -18000S
100s
09
Decel Time
0 1 s
0 1 -18000S
100s
10
DC Injection Braking Voltage
0 1 V
0 0 - 2000 V
15V
1 1
DC Injection Braking Time at stop
0 1 s
00-1000S
05s
12
DC Injection Braking Time at start
0 1 s
00-255s
00s
13
Freq Command Gain
001
001 -255
100
14
Freq Command Bias
01%
00-255%
0 0
1 5
Freq Command Upper Limit
1 %
0-110%
100
16
Freq Command Lower Limit
1 %
0-110%
0
1 7
Setting Prohibited Freq 1
0 1 Hz
0 0 - 40001-1z
0 0 Hz
18
Setting Prohibited Freq 2
0 1 Hz
0 0 - 400 0 Hz
0 0 Hz
19
Setting Prohibited Freq 3
0 1 Hz
0 0 - 400 0 Hz
0 0 Hz
20
Motor Rated Current
0 1 A
0 1 - 3600A
See Table 12 .
21
Carrier Freq Lower
1 Hz
380 - 2500 Hz
380 Hz
22
Torque Compensation Gain
0 1
00-99
1 0
23
Over Torque Detecting Level
1 %
30-200%
160%
24
Freq Monitor Gain
001
001 -200
100
25
Current Monitor Gain
001
001 -200
100
26
Inching Freq
0 1 Hz
0 0 - 400 0 Hz
6 0 Hz
27
Freq . Command 1 for Multi-step Run
0 1 Hz
0 0 - 40001-1z
1
0 0 Hz
28
Freq Command 2 for Multi-step Run
0 1 Hz
0 0 - 400 0 Hz
1
0 0 Hz
29
Accel/Decel Time
0 1 s
0 1 -18000S
100s
30
Save Energy Gain
1 %
0-120%
80%
31
Slip Compensation Gain
0 1
00-99
0 0
32
Speed Display(Freq, RPM, Speed %. etc)
1
0-39999
0
33
Optional Speed Agreed Frequency
0 1 Hz
0 0 - 4000 Hz
0 0 Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents