8-3-8.XC-E3AD4PT2DA
1
Brief Introduction
3CH 14bits current input、4CH PT100 temperature input and 2CH 10bits voltage output
3CH AD is current (0~20mA、4~20mA) selectable; 2Ch DA is voltage (0~5V、0~10V)
selectable, choose via the software;
Pt resistor input, the scale is PT100
3CH A/D and 4CH PT input are equipped with PID auto tune function;
As the special module, 7pcs XC-E3AD4PT2DA can be connected to one XC series PLC main
unit;
2
Specification
Items
Analogue input
DC0~20mA, 4~20mA
Temperature
testing range
Max input range
Analogue output
range
Digital input
range
Digital Output
14 bits Binary (0~16383)
Range
Distinguish Ratio
PID Output Value
Integral Precision
Convert Speed
Power Supply
Analogue Current Input
(AD)
-
DC0~40mA
-
-
1/16383(14Bit): The
converted data is stored
in PLC in Hex. (14Bit)
0~K4095
0.8%
20ms/CH
Temperature Input
(PT)
PT100
-100~350℃
-
-
-
-1000~3500
0.1℃
±0.5℃
DC24V±10%,100mA
8 expansion devices
Analogue Voltage
Output (DA)
-
-
-
DC0~5V,
0~10V(external load
resistor 2KΩ~1MΩ)
10 bits Binary (0~1023)
-
1/1023(10Bit): The
converted data is stored
in PLC in Hex. (10Bit)
-
0.8%
3ms/CH