4CH analogue input: voltage and current input selectable; Voltage input range is 0~5V, 0~
10V selectable, current input range is 0~20mA、4~20mA selectable;
14 bits high precision analogue input;
As the special module, 7pcs XC-E4AD can be connected to one XC series PLC main unit;
XC-E4AD module support PID auto tune function;
2
Specification
Items
Analogue Input Range
Max Input Range
Analogue Output
Range
Digital Input Range
Digital Output Range
Distinguish Ratio
PID Output Value
Integral precision
Convert Speed
Power Supply
3
Terminal Arrangement
CH
NAME SIGNAL
CH0 AI0
VI0
C0
CH2 AI2
VI2
C2
24V
-
0V
Voltage Input
DC0~5V, 0~10V
DC±18V
1/16383(14Bit); the convert data is stored in PLC in form of Hex. (14Bit)
Current analogue input CH1 AI1
Voltage analogue input
COM of CH0
Current analogue input CH3 AI3
Voltage analogue input
COM of CH2
+24V power supply
COM of power supply
Analogue Input (AD)
Current Input
DC0~20mA, 4~20mA
DC0~40mA
-
-
14 bits binary (0~16383)
0~K4095
(14Bit)
0.8%
20ms/CH
DC24V±10%, 100mA
CH
NAME SIGNAL
Current analogue input
VI1
Voltage analogue input
C1
COM of CH1
Current analogue input
VI3
Voltage analogue input
C3
COM of CH3