Xinje XC Series User Manual page 88

Plc hardware
Hide thumbs Also See for XC Series:
Table of Contents

Advertisement

2
Specification
Items
Analogue Input Signal
Temperature testing range
Digital Output range
Control precision
Distinguish Ratio
Integral Precision
Convert Speed
Power Supply
※1: When no signal input, the channel's data is 4095;
※2: According to the actual requirements, connect with the thermo-resistors;
3
Terminal Arrangement
CH
NAME SIGNAL
TC0+
CH0
TC0-
CH2 TC2+
TC2-
CH4 TC4+
TC4-
Y0~Y5
24V
0V
Specifications
K、S、E、N、J、T、R type thermocouples
0℃~1000℃
0~4095, without sign 12 bits, decimal
0.1℃
0.1℃
0.1℃
20ms/CH
DC24V±10%, 50mA
CH0 temperature input+
CH0 temperature input-
CH2 temperature input+
CH2 temperature input-
CH4 temperature input+
CH4 temperature input-
Output Channel Y0~Y5
Analogue Output: in the form of digital type, the range is 0~4095
Digital Output: in the form of occupy ratio, Y output in the activate time
+24V power supply
COM of power supply
CH
NAME
SIGNAL
CH1 TC1+
CH1 temperature input+
TC1-
CH1 temperature input-
CH3 TC3+
CH3 temperature input+
TC3-
CH3 temperature input-
CH5 TC5+
CH5 temperature input+
TC5-
CH5 temperature input-