Xinje XC Series User Manual page 66

Plc hardware
Hide thumbs Also See for XC Series:
Table of Contents

Advertisement

 Action display
LED lamp lights when output relay's coils galvanize, output contacts are ON.
 Response time
From the output relay galvanize (or cut) to the output contacts be ON (or OFF),
the response time is about 10ms
 Output current
The current-voltage below AC250V can drive the load of pure resistance 2A/1
point、 inductance load below 80VA (AC100V or AC200V) and lamp load below
100W(AC100V or AC200V).
 Open circuit's leak current
When the output contact be OFF and there's no leak current, can directly drive Ne
lamp etc.
 The life of relay output contacts
Standard life of induce AC load such as contactor、electromagnetism valve:5
million times for 20VA load. Cut power device's life according to the company's
test: for 80VA load, the action life is up to 2 million times. But if the load parallel
connection with surge absorber, the life will be greatly improved.
Output Connection