Display of input and output states

1. Selection of input or output type
Press RIGHT button longer than 2 sec.
➔SEL and Date or Time (alternately) is displayed.
Press UP button 3 times: SEL and UI are displayed. You are now in input or output mode to
recognize the current controller status. There are 4 different display options:
UI = Display of universal inputs
Ao = Display of analog outputs
FAN = Fan display
do = Display of digital, 3-point or PWM outputs
Note: The deactivated inputs are not displayed!
Continue with the RIGHT button.
2. Select number of in- or output
Press the UP or DOWN button to select the desired input or output.
Press RIGHT button to complete the process. The displayed image shows a universal output 1 with
a value of 25%. Universal input 2 is deactivated on the second image.
Pressing the LEFT button takes you to the higher level. Here you have the possibility to select the
different inputs and outputs.
The displayed values are not adjustable in this display but only visible!
3. Display total run time for binary outputs
Press RIGHT button longer than 2 sec.
➔SEL and Date or Time (alternately) is displayed.
Press UPPER or LOWER button until SEL and do are displayed. Then press the RIGHT button to go
to the desired output. Press the RIGHT key again to display the total runtime.
Press the LEFT key to return to the selection of inputs and outputs.
This display of a total runtime is only shown for digital outputs with an active time-of-flight meter.
Large digits show the selected output do01 - do06,
the small digits show the total running time in hours.
If the runtime is greater than 9999 hours, one bar appears on the right-hand side for every
10,000 hours.
The example on the right corresponds to 50345 hours runtime.
(Maximum term is 65535 hours = 7.5 years)
Doc : 70-00-0736, Serie X2, 20190206
subjects to alteration
© Vector Controls GmbH, Schweiz
www.vectorcontrols.com
X2-OPERATING MANUAL
See picture
1.1.
UI...
SEL
OP
LP...
UI 1
25
%
or
UI 2
OFF
do 1
345
h
Page 8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents