Vector OPA2 Series Operating Manual page 5

Operating instructions for the x2 operating system
Table of Contents

Advertisement

V
ECTOR
3. Create weekly time schedules
3.1. Press RIGHT button longer than 2 sec.
➔SEL and Date or Time (alternately) is displayed.
3.2. Press UP button
➔PRO und SEL is displayed.
Set time program to ON or OFF with RIGHT button
Change to Pr 01 - Pr 12 with the UP or DOWN button.
3.3. Press RIGHT button to select the following:
no = switching time not activated
OP = Operating mode ON (normal operation), ECO (reduced operation) or OFF
(protective operation)
LP = setpoint of a control loop (setting range from 0-100%)
AO = Positioning of the analog output (output must be in manual mode!)
FAN = Fan control (fan stages from FSP0-3 and Auto)
do = positioning of the digital output (output must be in manual mode!)
Hday = Annual time schedule. (holidays)
A function can be selected by pressing the UP or DOWN button.
Press RIGHT key to complete the selection.
4. Select a switching time
4.1. Press RIGHT button longer than 2 sec.
➔SEL and Date or Time (alternately) is displayed.
4.2. Press UP button ➔ PRO und SEL is displayed.
4.3. Press RIGHT button while PRO-ON or OFF is displayed:
Press UP or DOWN button to select between programs (point 3.3.) 1 - 12.
4.4.
Press the RIGHT button and select the desired program (e.g. Pr01),
Press the UP or DOWN button to scroll through the possible selections to see which function
(no/OP/LP... etc.) is to be assigned to e.g. Pr01.
In this case, the control loop (LP) on program 1 (Pr01) is selected.
(1.bar indicates that step 1 is complete).
Press the RIGHT button to set the desired time. This is done using the UP and DOWN buttons
from 00:00 - 23:45
(2. bars indicate that step 2 is complete).
Continue with RIGHT button.
5. Apply selected switching time (Annual schedule)
DAY1 and Pr01 are now displayed on the screen:
To execute the time program on Monday (Day1), press the UPPER button.
A triangle symbol appears on the 1
In order not to execute the time program on Monday, press the LOWER button. The
triangle symbol disappears.
Press the RIGHT button to go to the next day.
Repeat this procedure to set DAY2 - DAY7 (Tuesday to Sunday).
(3. bars indicate that step 3 is complete).
Continue with RIGHT button.
6. Select ID (For example: LP01)
For all mode changes, it is necessary to select the output or the control loop in this step.
For example, for setpoint LP01, LP02, etc. or for an output the number of the output to be
changed.
In this concrete example, LP01 (control loop 01) is set to Pr01 (program 01). The connection has
already been defined in point 4.4. There it is also possible to choose between the different
connections or outputs.
(4th bar indicates that step 4 is complete).
Continue with RIGHT button
7. Complete switching event
Press the UP or DOWN button to select the desired setpoint, operating mode or position of an
output. (See item 3.3 for more information on entering and selecting data)
(5. bars indicate that step 5 is complete).
After pressing the RIGHT key, you have returned to point 3.2. Now you can start creating the
weekly schedules for programs 2 - 12. Appropriate times, weekdays as well as control loops or
outputs can then be specified.
Doc : 70-00-0736, Serie X2, 20190206
subjects to alteration
© Vector Controls GmbH, Schweiz
www.vectorcontrols.com
X2-OPERATING MANUAL
See picture
1.1.
Pr01-12
SEL
LP...
OP
See picture
1.1.
2.2.
2.3.
3.2.
LP
Pr01
08:30
Pr01
dAY1
Pr01
1 2 3 4 5 6 7
LP01
Pr01
25
.
Pr01
0
%
Page 5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents