Idle Display; Power Failure - Vector OPA2 Series Operating Manual

Operating instructions for the x2 operating system
Table of Contents

Advertisement

V
ECTOR

Idle Display

The idle display is activated when no key has been pressed for 30 seconds.
The idle display can be deactivated by the technician. Last active control loop or manual output will remain displayed.
Display of control loop
Active when changing set points. Large digits show input value. Small digits show set point. Horizontal bars top left
show which loop is being displayed.
Override of secondary set point in cascade control
With cascade control, manual override of the secondary circuit can be activated. This is defined by the technician in
the controller settings.
If cascade control is active (with VAV for example) the user can override the primary loop and manually select the set
point of the secondary loop (the loop is then changed to constant air volume mode). This function is helpful for tuning
the VAV system. While the secondary loop is displayed change the set point with UP/DOWN. The hand symbol
appears. Change setpoint again to cancel cascade override. The hand symbol disappears.
Manual Mode
The hand symbol is displayed during a pending delay. For example, if a start-up delay is active. The controller
remains switched off and displays the hand symbol until the delay has elapsed. Then the controller switches on and
the hand symbol goes out.
Status-LED
A status LED is located on the upper left side of the controller housing. During normal operation the LED blinks
briefly once every 5 seconds. It will blink every second in case there is an alarm or fault condition.

Power Failure

All parameters and set points are memorized and do not need to be re-entered. The switch-on behaviour on return
of the power supply is set by the technician.
Clock and time schedule settings are retained for 48 hours after being powered for at least 10 hours.
Error Messages
Err1:
Communication error
Err2:
Internal error: Firmware version of the memory does not match firmware.
Err3:
Timer error: Set time and acknowledge error. If an error occurs again at a previously set time, the watch is
faulty. Time switching functions are not guaranteed in this case.
Err4:
Configuration error: An assigned input is not activated or has failed. Check all settings and ensure that all
inputs used are activated and functional.
Err5:
Copy error: Communication error with external memory AEC-PM1 or AEC-PM2.
Err6:
Copy error: Checksums of the data record are incorrect. The data record is invalid.
Doc : 70-00-0736, Serie X2, 20190206