Table 5- 5 Led Indicators For Firmware Update - Siemens Simatic S7-300 CP 341 User Manual

Point-to-point communication, installation and parameter assignment
Table of Contents

Advertisement

LED indicators
LED indicators when loading a firmware update:
Table 5- 5
LED indicators for firmware update
Status
Firmware update in progress
Firmware update completed
CP 341 without module
firmware
Hardware fault during firmware
update
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
Manual, 09/2008, A5E02191071-01
www.gkbpx.com
SF
TXD
RXD
On
On
On
On
Off
Off
Flashing
Off
Off
(2 Hz)
Flashing
Flashing
Flashing
(2 Hz)
(2 Hz)
(2 Hz)
Configuring and Parameter Assignment the CP 341
Comment
-
-
Module firmware
deleted, firmware update
canceled, firmware
update still possible
Delete/write operation
failed
该文档是极速PDF编辑器生成,
如果想去掉该提示,请访问并下载:
http://www.jisupdfeditor.com/
5.8 Firmware updates
Remedy
-
-
Reload the firmware
Switch power supply to
module off and then on
again and reload the
firmware.
Check whether the
module is defective.