Diagnostics with the CP 341
8.1 Diagnostics Functions of the CP 341
Event class 6 (06H):
"Error when processing a partner job" only for RK 512
Event no.
Event text
(06)01H
Error in 1st command byte (not 00 or FFH)
(06)02H
Error in 3rd command byte (not A, 0 or E)
(06)03H
Error in 3rd command byte in the case of
continuation message frames (command not as
for 1st message frame)
(06)04H
Error in 4th command byte (command letter
incorrect)
(06)05H
Error in 4th command byte in the case of
continuation message frames (command not as
for 1st message frame)
(06)06H
Error in 5th command byte (DB number not
permissible)
(06)07H
Error in the 5th or 6th command byte (start
address too high)
(06)08H
Error in 7th or 8th command byte (impermissible
length)
(06)09H
Error in 9th and 10th command byte
(coordination flag for this data type impermissible
or bit number too high)
(06)0AH
Error in the 10th command byte (illegal CPU
number)
(06)0BH
SEND message frame was longer/shorter than
expected (more/less data received than
announced in message frame header).
(06)0CH
FETCH command message frame with user data
received.
(06)0DH
The CP received a message frame during an
invalid operating mode:
Receive connection between the CPU and
CP is not set up or not yet correctly set up
CP startup is not fully completed
The receiving CPU is in STOP mode
Parameters of the addressed interface are
currently being reassigned
192
www.gkbpx.com
Remedy
Basic header structure error on partner. Check for
malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
Basic header structure error on partner. Check for
malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
Basic header structure error on partner. Check for
malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
Header layout error at partner or a command
combination has been requested that is not permitted
at the CP. Check the permissible commands. Check
for malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
Basic header structure error on partner. Check for
malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
Refer to the request tables for the permissible DB
numbers, start addresses, or lengths.
Refer to the request tables for the permissible DB
numbers, start addresses, or lengths.
Obtain from the request tables the permissible DB/DX
numbers, start addresses or lengths.
Basic header structure error on partner. Refer to the
request tables for when a coordination flag is
permitted.
Header layout error at partner
Correction required at the partner
Correction required at the partner
Check whether the addressed connection has been
assigned the correct parameters
This error message can only occur only during
CP startup. Repeat the request.
Place the CPU back in RUN mode and repeat the
request.
This is a temporary error. Repeat the request.