Optional Accessories - Eaton W-VACi User Manual

12/17.5/24 kv iec vacuum circuit breakers
Table of Contents

Advertisement

7.4

Optional accessories

Shunt Opening Release #2 (ST2)
Like the shunt opening release, this device allows for remote opening control of the circuit breaker. It can be
supplied by a circuit completely independent from the shunt opening release #1.
24 VDC / 8.9A
48 VDC / 4.4A
60 VDC / 4.3A
110-125 VDC / 2.7A
220-250 VDC / 1.5A
110-120 VAC / 2.6A
220-230 VAC / 1.4A
Attributes
Ua (DC)
Ua (AC)
Operating Limits
Insulating voltage
Mechanism Electromagnetic Interlock (IC1)
This device protects the operating mechanism from being unsafely activated in the event that the control circuit is
not energized.
24 VDC
48 VDC
60 VDC
110-125 VDC
220-250 VDC
110-120 VAC
220-230 VAC
Attributes
Ua (DC)
Ua (AC)
Operating Limits
Continuous Power (Pc)
Insulating voltage
Table 7-2 Optional Accessories
65A7003G01
65A7003G02
65A7003G13
65A7003G04
65A7003G06
65A7003G10
65A7003G12
65A7019G01
65A7019G02
65A7019G13
65A7019G04
65A7019G06
65A7019G10
65A7019G12
65A7355H01 November 2011 www.eaton.com
24-48-60-110-125-220-250 V
110-120-220-230 V
70...110% Ua (DC)
85...110% Ua (AC)
2000 V 50/60 Hz (for 1 min.)
24-48-60-110-125-220-250 V
110-120-220-230 V
85...110% Ua
DC= 5 W
AC= 5 VA
2000 V 50/60 Hz (for 1 min.)
67

Hide quick links:

Advertisement

Table of Contents
loading