Terminal and lead-through data for the control cables

I/O cables
Aux. power cables

AC output connection specification

Voltage
Allowed electrical system
type
Transformer
Short-circuit withstand
strength (IEC 60439-1)
Frequency
Imbalance
Voltage dips
Fundamental power factor
(cos phi
)
1
Cable outer diameter:
• 5...7 mm 6 pcs
• 10...14 mm 2 pcs
Max. conductor size: 1.5 mm
Tightening torques: 0.2 – 0.4 Nm
Cable outer diameter:
• 20...26 mm 2 pcs
• 10...14 mm 2 pcs
Tightening torques: *M12 70 Nm
PVS800-57B-1645kW-C: 380 V AC 3-phase +/- 10%
PVS800-57B-1732kW-C: 400 V AC 3-phase +/- 10%
3-phase IT (ungrounded) system. Galvanic isolation for each inverter is
needed.
The transformer must be suitable for IGBT-based inverter use with high du/dt
values against the ground. Dedicated low-voltage winding is needed for each
inverter. Static screen between windings with proper dimensioning is
needed.
For details on selecting the transformer, refer to
page 33.
Maximum allowable prospective short-circuit current is 50 kA when protected
by fuses given in fuse tables.
When temporary grounding for work is applied (one set of grounding cables
are connected to the connecting knobs of the AC and DC busbars and PE of
the inverter): the maximum allowable prospective short-circuit current is
decreased to 40 kA / 1 s. If the connected grounding cables and clamps are
not equivalent to the prospective short-circuit rating of the inverter, the total
rating will be lower.
45 to 65 Hz withstand with normal dimensioning (grid-compliance may
require disconnection at smaller values.) Maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase AC line voltage
Max. 0%
1
2
/AWG 16
Selecting the transformer
Technical data 53